Host Types
Component | Description | |||||
---|---|---|---|---|---|---|
Instance Type | G1s.small | M1s.medium | M1d.medium | X1d.xLarge | M1d.xLarge | M1d.xSmall |
Chassis | 1U1N (Dell VxRail E560F) | 1U1N (Dell VxRail E560F) | 1U1N (Dell VxRail E560N) | 1U1N (Dell VxRail E560F) | 1U1N (Dell VxRail E560F) | 1U1N (VxRail E560F) |
CPU Sockets | 1 | 1 | 2 | 2 | 2 | 2 |
CPU Cores | 28 | 28 | 56 | 56 | 56 | 56 |
vCPU Cores | 56 | 56 | 112 | 112 | 112 | 112 |
CPU Frequency/Cache | 2.2 GHz All Core Turbo | 2.2 GHz All Core Turbo | 2.2 GHz All Core Turbo | 2.2 GHz All Core Turbo | 2.2 GHz All Core Turbo | 2.2 GHz All Core Turbo |
RAM | 256 GB | 384 GB | 768 GB | 1536 GB | 768 GB | 768 GB |
Cache SSD | 1.6 TB SSD SAS | 1.6 TB SSD SAS | 3.2 TB NVMe | 3.2 TB NVMe | 3.2 TB NVMe | 1.6 TB SSD SAS |
Primary Storage | 11.5 TB SSD | 23 TB SSD | 23 TB NVMe | 61 TB SSD | 61 TB SSD | 3.8 TB SAS |
Disk Groups | 2 | 2 | 2 | 2 | 2 | 2 |
Power Supplies | Redundant x 1100 W 100-240v and 400-415v | Redundant x 1100 W 100-240v and 400-415v | Redundant x 1100 W 100-240v and 400-415v | Redundant x 1100 W 100-240v and 400-415v | Redundant x 1100 W 100-240v and 400-415v | Redundant x 1100 W 100-240v and 400-415v |
Rack Infrastructure
Component | R2.220V (Single-phase) and R2.220V (Three-phase) |
---|---|
Usable hosts per rack type | R2.220v (single-phase):
R2.220v (three-phase) and R2.400v (three-phase):
|
Standard host per rack type Standard host is the spare host used for life-cycle management. |
1 |
Multi-rack scale | Up to 3 racks, including multi-rack aware single rack |
SD-WAN | Redundant VMware SD-WAN |
Network Fabric |
|
Management Switch | 1 x 1 Gbps switch |
Customer-Facing Uplinks |
|
UPS | Not applicable |
PDU | Redundant smart PDUs |
Rack Appliance Dimensions
Dimension | R2.220V (Single-phase) | R2.220V (Three-phase) |
---|---|---|
Width | 23.62 inches | 23.62 inches |
Depth | 47.24 inches | 47.24 inches |
Height | 78.39 inches | 78.39 inches |
Rack Appliance Power and Weight Characteristics
R2 with M1d.medium Hosts | |||
Estimated Input Power in Watts | 3,367 | 3,972 | 4,577 |
Input Current Amps at 208v)-Max | 16.2 | 19.1 | 22 |
Heat Output (BTU/hr)-Max | 11,481 | 13,545 | 15,608 |
Weight in Pounds | 618 | 666 | 714 |
Power Requirements
Component | R2.220V (Single-phase) | R2.220V (Three-phase) | R2.400V (Three-phase) |
---|---|---|---|
Power voltage | Between 200-240 volts | Between 200-240 volts | Between 400-415 volts |
PDU | 4 x 30A single phase Smart PDU | 4 x 30A 3-phase smart PDU | 4 x 20A 3-phase smart PDU |
Circuit | 4 x 30 Amps |
4 x 30 Amps |
4 x 20 Amps |
Power Socket | 4 x NEMA L6-30 30A | 4xNEMA L21-30 30A | 4 x IEC 60309 20A 3P+N+PE |
Power Source Distance | 10 feet from the top or bottom of the rack | 6 feet from the top or bottom of the rack | 6 feet from the top or bottom of the rack |
Environmental Requirements
Component | R2.220V (Single-phase) and R2.220V (Three-phase) |
---|---|
Operating temperature | 10–30°C (50–86°F) with no direct sunlight on the equipment. |
Storage temperature range | -40°C to +65°C (-40°F to +149°F) |
Operating relative humidity | 10–80 percent (non-condensing) |
Operating altitude with no deratings | 3048m (approximately 10,000 feet) |
Networking Requirements
Ports | The following ports are open for connecting your SDDC to VMware Cloud:
|
||||||||||
Data ToRs |
|
||||||||||
SD-WAN devices by VeloCloud |
|
||||||||||
Subnets |
VMware Cloud on Dell EMC requires three subnets for management.
|